Multi-Protocol Remote I/O Module Reference Design
An illustrative remote I/O module design (bus coupler + on-board I/O) for distributed signal acquisition on production lines, machine tools and conveyors: DC 24V supply (separate system supply Us / field supply Up), dual RJ45 10/100 ports for line topology, running EtherCAT / PROFINET / Modbus TCP depending on firmware; on-board 8 × 24V digital inputs, 8 digital outputs, 4 analog inputs and 2 analog outputs (isolated), backplane bus for expansion I/O modules, and a Type-C configuration port. This page covers the function, selection notes and available VOOHU parts for 30 component positions.
Illustrative PCB ⇄ Schematic
The illustrative layout shows placement and component positions; click any position to see its selection notes, recommended parts and package. The board view is an illustration neatly arranged by functional zone (not the actual layout); the Ethernet ports, I/O terminals, backplane connector, configuration port and power terminal sit along the bottom edge, and the expansion I/O modules are external nodes.
The two ports (IN / OUT) are identical, so the diagram shows 1 port and 1 differential pair (the other 10/100 pair is the same). RJ45 J1 / J2 are plain jacks without magnetics; after the VOOHU discrete 10/100 LAN transformers T1 / T2 (WHS16037TG, 1500 Vrms isolation), the PHY-side pairs are clamped by ESD arrays D1 / D2 (WHALD03G4U) and go to the JL1111BI-NI 10/100 PHY, which connects over MII to the communication controller (EtherCAT / PROFINET real-time Ethernet needs MII); 25MHz crystal Y1 provides the reference clock. Center-tap wiring, termination and load capacitor values per the PHY datasheet.
Board bill of materials
Click any row to jump to that position and view its selection notes
| No. | Zone | Position | Ref. | VOOHU category | Recommended part | Availability |
|---|---|---|---|---|---|---|
| 01 | A Dual Ethernet | RJ45 port ×2 (IN / OUT, with LEDs) | J1 J2 | RJ45 Connectors | SYT561188AB1A1DB4 | VOOHU |
| 02 | A Dual Ethernet | 10/100 LAN transformer ×2 | T1 T2 | 10/100 BASE-TX | WHS16037TG | VOOHU |
| 03 | A Dual Ethernet | Ethernet ESD array ×2 | D1 D2 | TVS / ESD | WHALD03G4U | VOOHU |
| 04 | A Dual Ethernet | 10/100 PHY ×2 (MII) | U1 U2 | Ethernet PHY | JL1111BI-NI | VOOHU |
| 05 | A Dual Ethernet | PHY 25MHz crystal | Y1 | — | — | Non-VOOHU |
| 06 | B Digital I/O | DI terminal (8 × 24V inputs) | J3 | — | — | Non-VOOHU |
| 07 | B Digital I/O | DI input TVS | D3 | TVS / ESD | WHALD30E2B | VOOHU |
| 08 | B Digital I/O | DI optocoupler isolation | U3 | — | — | Non-VOOHU |
| 09 | B Digital I/O | DO terminal (8 × 24V outputs) | J4 | — | — | Non-VOOHU |
| 10 | B Digital I/O | Isolated high-side switch (8-channel) | U4 | — | — | Non-VOOHU |
| 11 | C Analog I/O | AI / AO terminal (4AI / 2AO) | J5 | — | — | Non-VOOHU |
| 12 | C Analog I/O | AI / AO port TVS | D4 | TVS / ESD | WHALD30E2B | VOOHU |
| 13 | C Analog I/O | Analog front end (ADC + DAC) | U5 | — | — | Non-VOOHU |
| 14 | C Analog I/O | SPI digital isolator | U6 | — | — | Non-VOOHU |
| 15 | C Analog I/O | Push-pull isolated power transformer | T3 | Push-Pull Transformers | WHST06K02A0 | VOOHU |
| 16 | C Analog I/O | Push-pull driver + isolated-side LDO | U7 U8 | — | — | Non-VOOHU |
| 17 | D Backplane · Config | Backplane bus transceiver | U9 | — | — | Non-VOOHU |
| 18 | D Backplane · Config | Backplane bus ESD array | D5 | TVS / ESD | WHTA5V01P2C | VOOHU |
| 19 | D Backplane · Config | Backplane bus connector | J6 | — | — | Non-VOOHU |
| 20 | D Backplane · Config | USB Type-C configuration port (USB 2.0 only) | J7 | USB / Type-C | WHTCAX01167303 | VOOHU |
| 21 | D Backplane · Config | USB ESD array | D6 | TVS / ESD | WHTA5V01P2C | VOOHU |
| 22 | E Core | Multi-protocol industrial Ethernet communication controller | U10 | — | — | Non-VOOHU |
| 23 | E Core | Firmware / parameter Flash | U11 | — | — | Non-VOOHU |
| 24 | E Core | MCU crystal | Y2 | — | — | Non-VOOHU |
| 25 | E Core | Core supply filter molded inductor ×2 | L1 L2 | Molded Inductors | WHYTA0420 Series | VOOHU |
| 26 | F Power | DC 24V power terminal (Us / Up) | J8 | — | — | Non-VOOHU |
| 27 | F Power | Input fuse + TVS | F1 D7 | TVS / ESD | WHTB058VA | VOOHU |
| 28 | F Power | Power line common-mode choke (EMI) | L3 | Power Line CMC | WHAL-7060A-102T0 | VOOHU |
| 29 | F Power | Synchronous buck ×2 (24V→5V→3.3V) | U12 U13 | — | — | Non-VOOHU |
| 30 | F Power | DC-DC molded inductor ×2 | L4 L5 | Molded Inductors | WHYT0630 Series | VOOHU |
Resources & downloads
Board bill of materials
Reference designators, zones, VOOHU categories, recommended parts and availability for all 30 positions. Opens directly in Excel.
Datasheet collection
Datasheet PDFs for the VOOHU parts recommended on this board.
Design files & footprint library
Schematic, PCB, and VOOHU part footprints and 3D models.
Coming soonRequest the remote I/O module reference design full package
Includes the BOM, datasheets for the recommended VOOHU parts and position-by-position selection notes. For selection advice tailored to your fieldbus protocol, I/O count or isolation requirements, please include it in your requirements. We reply within 24 hours on working days.