Intelligent Motor Protector Reference Design
Illustrative design of an intelligent motor protector for motor feeders in low-voltage switchgear (MCC): DC 24V control supply, external three-phase current transformers and motor PTC for overload, phase-loss and stall protection, relay outputs driving the contactor coil directly, and digital inputs for start/stop buttons and contactor auxiliary contacts; dual RJ45 Ethernet ports (3+1-port 100M switch for in-cabinet daisy-chaining) and isolated RS-485 (Modbus RTU) for data upload, with an external operator panel connected via an RJ45 port. This page covers the function, selection notes and available VOOHU parts for all 31 component positions.
Illustrative PCB ⇄ Schematic
The illustrative layout shows placement and component positions; click any position to see selection notes, recommended parts and package. The board is arranged by functional zone for illustration (not the actual layout); Ethernet ports, RS-485, panel port, measurement / DI / relay terminals and power terminal all sit on the bottom edge, while current transformers, contactor and motor are external nodes.
Both ports are identical; only one port and one differential pair are drawn (the other 100M pair is the same). J1 is a dual RJ45 with integrated magnetics and CMCs; the PHY-side pairs are clamped by ESD arrays D1 / D2 and go to the copper ports of the JL5104C-NI (3+1-port 100M switch with built-in PHYs). The switch's third port connects to the MCU via RMII, and frames between the two ports are forwarded by the switch directly for in-cabinet daisy-chaining. Centre-tap connection, termination and crystal load capacitors per the JL5104 datasheet.
Board bill of materials
Click any row to jump to that position and view its selection notes
| No. | Zone | Position | Ref. | VOOHU category | Recommended part | Availability |
|---|---|---|---|---|---|---|
| 01 | A Dual Ethernet | Dual RJ45 (integrated magnetics, daisy chain) | J1 | RJ45 Connectors | SYT212B579CD2A4D | VOOHU |
| 02 | A Dual Ethernet | Ethernet ESD array ×2 | D1 D2 | TVS / ESD | WHALD03G4U | VOOHU |
| 03 | A Dual Ethernet | 3+1-port 100M switch IC | U1 | Ethernet Switch | JL5104C-NI | VOOHU |
| 04 | A Dual Ethernet | Switch 25MHz crystal | Y1 | — | — | Non-VOOHU |
| 05 | B RS-485 · Panel | RS-485 terminal | J2 | — | — | Non-VOOHU |
| 06 | B RS-485 · Panel | Gas discharge tube (stage 1) | G1 | GDT | WHGD200V1P0B | VOOHU |
| 07 | B RS-485 · Panel | Bus TVS (stage-2 clamp) | D3 | TVS / ESD | WHALD30E2B | VOOHU |
| 08 | B RS-485 · Panel | Bus differential-line CMC | L1 | Signal Line CMC | WHAC-4532A-601ZP0 | VOOHU |
| 09 | B RS-485 · Panel | Isolated RS-485 transceiver | U2 | — | — | Non-VOOHU |
| 10 | B RS-485 · Panel | External operator panel RJ45 port | J3 | RJ45 Connectors | WH56A3188C011101 | VOOHU |
| 11 | B RS-485 · Panel | Panel port ESD | D4 | TVS / ESD | WHALD30E2B | VOOHU |
| 12 | B RS-485 · Panel | Panel RS-485 transceiver | U3 | — | — | Non-VOOHU |
| 13 | C Sensing · I/O | CT / PTC input terminal | J4 | — | — | Non-VOOHU |
| 14 | C Sensing · I/O | Three-phase current AFE | U4 | — | — | Non-VOOHU |
| 15 | C Sensing · I/O | Digital input terminal (DI) | J5 | — | — | Non-VOOHU |
| 16 | C Sensing · I/O | DI input TVS | D5 | TVS / ESD | WHALD30E2B | VOOHU |
| 17 | C Sensing · I/O | DI optocoupler isolation | U5 | — | — | Non-VOOHU |
| 18 | C Sensing · I/O | Relay outputs ×2 (with driver) | U6 K1 K2 | — | — | Non-VOOHU |
| 19 | C Sensing · I/O | Relay output terminal | J6 | — | — | Non-VOOHU |
| 20 | D Core | MCU | U7 | — | — | Non-VOOHU |
| 21 | D Core | Parameter / event storage (Flash) | U8 | — | — | Non-VOOHU |
| 22 | D Core | MCU crystal | Y2 | — | — | Non-VOOHU |
| 23 | D Core | Run / fault indicators | LED1 LED2 | — | — | Non-VOOHU |
| 24 | D Core | Core supply filter molded inductor ×2 | L2 L3 | Molded Inductors | WHYTA0420 Series | VOOHU |
| 25 | E Power | DC 24V control supply terminal | J7 | — | — | Non-VOOHU |
| 26 | E Power | Input fuse + TVS | F1 D6 | TVS / ESD | WHTB058VA | VOOHU |
| 27 | E Power | Power line common-mode choke (EMI) | L4 | Power Line CMC | WHAL-7060A-102T0 | VOOHU |
| 28 | E Power | Synchronous buck ×2 (24V→5V→3.3V) | U9 U10 | — | — | Non-VOOHU |
| 29 | E Power | DC-DC molded inductor ×2 | L5 L6 | Molded Inductors | WHYT0630 Series | VOOHU |
| 30 | E Power | Push-pull isolated power transformer | T1 | Push-Pull Transformers | WHST06K14A0 | VOOHU |
| 31 | E Power | Push-pull driver + isolated-side LDO | U11 U12 | — | — | Non-VOOHU |
Resources & downloads
Board bill of materials
Reference designators, zones, VOOHU categories, recommended parts and availability for all 31 positions. Opens directly in Excel.
Datasheet collection
Datasheet PDFs for the VOOHU parts recommended on this board.
Design files & footprint library
Schematic, PCB, and VOOHU part footprints and 3D models.
Coming soonRequest the motor protector reference design full package
Includes the BOM, datasheets of the recommended VOOHU parts and position-by-position selection notes. If you need advice for your protocol, port count or field protection requirements, describe them in the request. We reply within 24 hours on working days.