Bay Control Unit Reference Design
Illustrative reference design of the CPU module of a bay control unit (measurement & control device) for the bay level of a smart substation: the SoC handles telemetry, teleindication, remote control, remote adjustment and synchro-check closing; the station bus reports to the SCADA backend and telecontrol via MMS over dual A / B 100M copper ports, the process bus exchanges GOOSE (switch positions and control commands) over a 100Base-FX optical port, and an isolated RS-485 serves as the maintenance / protocol serial port; IRIG-B time sync gives 1 ms SOE resolution. The AC sampling module (power-frequency CT / PT and ADC), binary I/O module and power module are not on this board. Each position is marked with the VOOHU part available, recommended part numbers and package pinout.
Illustrative PCB ⇄ Schematic
Illustrative top-side view arranged by functional zone (not the actual layout). Red numbered dots mark positions VOOHU can supply. Click a component on the board, an entry in the index below or a part in the schematic to see recommended parts and package pinouts on the right.
MMS network A reference topology: the SoC connects over RMII to 10/100 PHY U4 (JL1111B-NI), then through ESD D1 (WHALD03G4U) and VOOHU single-port LAN transformer T1 (WHS16037TG) to RJ45 J1; the cable-side center tap goes to chassis ground through 75Ω×2 + 1nF/2kV and the PHY-side center tap to ground through 0.1µF. Only 1 differential pair is drawn; the PHY crystal, series resistors and decoupling are omitted.
Board bill of materials
Summarized by position; click any row to locate it on the board above.
| No. | Zone | Position | Ref. | VOOHU category | Recommended part | Availability |
|---|---|---|---|---|---|---|
| 01 | A Station Bus MMS ×2 | RJ45 port (station bus network A) | J1 | RJ45 Connectors | SYT561188GWA3DY1027 | VOOHU |
| 02 | A Station Bus MMS ×2 | 10/100 LAN transformer (network A) | T1 | LAN Transformers | WHS16037TG | VOOHU |
| 03 | A Station Bus MMS ×2 | MMS network A ESD array | D1 | TVS / ESD | WHALD03G4U | VOOHU |
| 04 | A Station Bus MMS ×2 | 10/100 Ethernet PHY (network A) | U4 | Ethernet PHY | JL1111B-NI | VOOHU |
| 05 | A Station Bus MMS ×2 | RJ45 port (station bus network B) | J2 | RJ45 Connectors | SYT561188GWA3DY1027 | VOOHU |
| 06 | A Station Bus MMS ×2 | 10/100 LAN transformer (network B) | T2 | LAN Transformers | WHS16037TG | VOOHU |
| 07 | A Station Bus MMS ×2 | MMS network B ESD array | D2 | TVS / ESD | WHALD03G4U | VOOHU |
| 08 | A Station Bus MMS ×2 | 10/100 Ethernet PHY (network B) | U5 | Ethernet PHY | JL1111B-NI | VOOHU |
| 09 | B Maint. Serial / GOOSE | RS-485 terminal (maintenance / protocol) | J3 | — | — | Non-VOOHU |
| 10 | B Maint. Serial / GOOSE | Maintenance RS-485 CMC | L1 | Signal Line CMC | WHAC-4532A-510U0 | VOOHU |
| 11 | B Maint. Serial / GOOSE | Maintenance RS-485 ESD / TVS | D3 | TVS / ESD | WHALD30E2B | VOOHU |
| 12 | B Maint. Serial / GOOSE | Isolated RS-485 transceiver | U6 | — | — | Non-VOOHU |
| 13 | B Maint. Serial / GOOSE | GOOSE optical port SFP cage + host connector | J4 | SFP Series | WH81-111-Y0016-1 | VOOHU |
| 14 | B Maint. Serial / GOOSE | Optical module supply filter inductor | L2 | Molded Inductors | WHYTA0420 Series | VOOHU |
| 15 | B Maint. Serial / GOOSE | 10/100 PHY (100Base-FX fiber mode) | U7 | Ethernet PHY | JL1111B-NI | VOOHU |
| 16 | C IRIG-B time sync | IRIG-B time-sync terminal (RS-485 differential B code) | J5 | — | — | Non-VOOHU |
| 17 | C IRIG-B time sync | IRIG-B time-sync line CMC | L3 | Signal Line CMC | WHAC-4532A-510U0 | VOOHU |
| 18 | C IRIG-B time sync | IRIG-B time-sync ESD / TVS | D4 | TVS / ESD | WHALD30E2B | VOOHU |
| 19 | C IRIG-B time sync | IRIG-B isolated receiver (RS-485) | U8 | — | — | Non-VOOHU |
| 20 | C IRIG-B time sync | Push-pull driver + rectifier / LDO | U9 | — | — | Non-VOOHU |
| 21 | C IRIG-B time sync | Push-pull isolation transformer | T3 | Push-Pull Transformers | WHST06Q06A0 | VOOHU |
| 22 | D CPU / FPGA | SoC + FPGA (four remote + synchro-check + MMS) | U1 | — | — | Non-VOOHU |
| 23 | D CPU / FPGA | DDR memory | U2 | — | — | Non-VOOHU |
| 24 | D CPU / FPGA | Flash storage | U3 | — | — | Non-VOOHU |
| 25 | E Module Power | Backplane power (+24 V from power module) | J6 | — | — | Non-VOOHU |
| 26 | E Module Power | Input power-line common-mode choke | L4 | Power Line CMC | WHAL-7060A-701T0 | VOOHU |
| 27 | E Module Power | Buck converter (24 V → 5 V) | U10 | — | — | Non-VOOHU |
| 28 | E Module Power | Buck converter (5 V → 3.3 V / core) | U11 | — | — | Non-VOOHU |
| 29 | E Module Power | Molded inductors ×2 (DC-DC) | L5 L6 | Molded Inductors | WHYT0630 Series | VOOHU |
Resources & downloads
Board bill of materials
Reference designators, zones, VOOHU categories, recommended parts and availability for all 29 positions. Opens directly in Excel.
Datasheet collection
Datasheet PDFs for the VOOHU parts recommended on this board.
Design files & footprint library
Schematic, PCB, and VOOHU part footprints and 3D models.
Coming soonRequest the full bay control unit reference design packagefull package