Substation Protection Relay Reference Design
Illustrative reference design of the CPU module of a line / transformer protection relay for the bay level of a smart substation: an SoC + FPGA runs differential, distance and zero-sequence protection logic; the station bus reports events and settings via MMS over dual A / B 100M copper ports, while the process bus receives SV sampled values from merging units and sends GOOSE trip commands to intelligent terminals over two 100Base-FX optical ports; IRIG-B differential B-code time sync. In conventional-sampling substations the analog quantities come from the AC module (power-frequency CT / PT and ADC); the AC module, binary I/O module and power module are not on this board. Each position is marked with the VOOHU part available, recommended part numbers and package pinout.
Illustrative PCB ⇄ Schematic
Illustrative top-side view arranged by functional zone (not the actual layout). Red numbered dots mark positions VOOHU can supply. Click a component on the board, an entry in the index below or a part in the schematic to see recommended parts and package pinouts on the right.
MMS network A reference topology: the SoC connects over RMII to 10/100 PHY U4 (JL1111B-NI), then through ESD D1 (WHALD03G4U) and VOOHU single-port LAN transformer T1 (WHS16037TG) to RJ45 J1; the cable-side center tap goes to chassis ground through 75Ω×2 + 1nF/2kV and the PHY-side center tap to ground through 0.1µF. Only 1 differential pair is drawn; the PHY crystal, series resistors and decoupling are omitted.
Board bill of materials
Summarized by position; click any row to locate it on the board above.
| No. | Zone | Position | Ref. | VOOHU category | Recommended part | Availability |
|---|---|---|---|---|---|---|
| 01 | A Station Bus MMS ×2 | RJ45 port (station bus network A) | J1 | RJ45 Connectors | SYT561188GWA3DY1027 | VOOHU |
| 02 | A Station Bus MMS ×2 | 10/100 LAN transformer (network A) | T1 | LAN Transformers | WHS16037TG | VOOHU |
| 03 | A Station Bus MMS ×2 | MMS network A ESD array | D1 | TVS / ESD | WHALD03G4U | VOOHU |
| 04 | A Station Bus MMS ×2 | 10/100 Ethernet PHY (network A) | U4 | Ethernet PHY | JL1111B-NI | VOOHU |
| 05 | A Station Bus MMS ×2 | RJ45 port (station bus network B) | J2 | RJ45 Connectors | SYT561188GWA3DY1027 | VOOHU |
| 06 | A Station Bus MMS ×2 | 10/100 LAN transformer (network B) | T2 | LAN Transformers | WHS16037TG | VOOHU |
| 07 | A Station Bus MMS ×2 | MMS network B ESD array | D2 | TVS / ESD | WHALD03G4U | VOOHU |
| 08 | A Station Bus MMS ×2 | 10/100 Ethernet PHY (network B) | U5 | Ethernet PHY | JL1111B-NI | VOOHU |
| 09 | B Process Bus GOOSE / SV | SFP cage + host connector (optical port 1) | J3 | SFP Series | WH81-111-Y0016-1 | VOOHU |
| 10 | B Process Bus GOOSE / SV | Optical module supply filter inductor (port 1) | L1 | Molded Inductors | WHYTA0420 Series | VOOHU |
| 11 | B Process Bus GOOSE / SV | 10/100 PHY (optical port 1 · FX mode) | U6 | Ethernet PHY | JL1111B-NI | VOOHU |
| 12 | B Process Bus GOOSE / SV | SFP cage + host connector (optical port 2) | J4 | SFP Series | WH81-111-Y0016-1 | VOOHU |
| 13 | B Process Bus GOOSE / SV | Optical module supply filter inductor (port 2) | L2 | Molded Inductors | WHYTA0420 Series | VOOHU |
| 14 | B Process Bus GOOSE / SV | 10/100 PHY (optical port 2 · FX mode) | U7 | Ethernet PHY | JL1111B-NI | VOOHU |
| 15 | C IRIG-B time sync | IRIG-B time-sync terminal (RS-485 differential B code) | J5 | — | — | Non-VOOHU |
| 16 | C IRIG-B time sync | IRIG-B time-sync line CMC | L3 | Signal Line CMC | WHAC-4532A-510U0 | VOOHU |
| 17 | C IRIG-B time sync | IRIG-B time-sync ESD / TVS | D3 | TVS / ESD | WHALD30E2B | VOOHU |
| 18 | C IRIG-B time sync | IRIG-B isolated receiver (RS-485) | U8 | — | — | Non-VOOHU |
| 19 | C IRIG-B time sync | Push-pull driver + rectifier / LDO | U9 | — | — | Non-VOOHU |
| 20 | C IRIG-B time sync | Push-pull isolation transformer | T3 | Push-Pull Transformers | WHST06Q06A0 | VOOHU |
| 21 | D CPU / FPGA | SoC + FPGA (protection logic + GOOSE / SV) | U1 | — | — | Non-VOOHU |
| 22 | D CPU / FPGA | DDR memory | U2 | — | — | Non-VOOHU |
| 23 | D CPU / FPGA | Flash storage | U3 | — | — | Non-VOOHU |
| 24 | E Module Power | Backplane power (+24 V from power module) | J6 | — | — | Non-VOOHU |
| 25 | E Module Power | Input power-line common-mode choke | L4 | Power Line CMC | WHAL-7060A-701T0 | VOOHU |
| 26 | E Module Power | Buck converter (24 V → 5 V) | U10 | — | — | Non-VOOHU |
| 27 | E Module Power | Buck converter (5 V → 3.3 V / core) | U11 | — | — | Non-VOOHU |
| 28 | E Module Power | Molded inductors ×2 (DC-DC) | L5 L6 | Molded Inductors | WHYT0630 Series | VOOHU |
Resources & downloads
Board bill of materials
Reference designators, zones, VOOHU categories, recommended parts and availability for all 28 positions. Opens directly in Excel.
Datasheet collection
Datasheet PDFs for the VOOHU parts recommended on this board.
Design files & footprint library
Schematic, PCB, and VOOHU part footprints and 3D models.
Coming soonRequest the full protection relay reference design packagefull package
Includes the board position list, datasheets of recommended VOOHU parts and per-position selection notes. For advice on your relay type (line / transformer / busbar), optical port count or Ethernet isolation level, describe them in the request. We reply within 24 hours on working days.